 G-TRIP CHARACTERISTICS
Application Examples:
ONE POLE
ONE POLE PLUS NEUTRAL
General industrial, including motors, some transformers, solenoids, control circuits, lighting and wiring. Meets the US trip norms with relatively short thermal trip delay and high magnetic trip point.
Type Designation 2 -- (a) G -- (b) N -- (c) U -- (d) 60 -- (e)
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 277VAC
1G
Type/ Cat. No. 1GU03 1GU05 NA 1GU08 1GU1 1GU1.6 1GU2 1GU2.5 1GU3 1GU3.5 1GU4 1GU5 1GU6 1GU8 1GU10 1GU12 1GU125 1GU13 1GU15 1GU16 1GU20 1GU25 1GU30 1GU32 1GU40 1GU50 1GU60 1GU63 Approvals
UL UL
2GN
Type/ Cat. No. 2GNU03 2GNU05 NA 2GNU08 2GNU1 2GNU1.6 2GNU2 2GNU2.5 2GNU3 2GNU3.5 2GNU4 2GNU5 2GNU6 2GNU8 2GNU10 2GNU12 2GNU125 2GNU13 2GNU15 2GNU16 2GNU20 2GNU25 2GNU30 2GNU32 2GNU40 2GNU50 2GNU60 2GNU63 277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/0.3A - 32A = 1.3kg (2.9 lb.) 40A - 63A = 1.45kg (3.2 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Approvals
UL UL
(a) = Number of Poles (b) = Trip Characteristic (c) = Blank: without neutral pole = N: with neutral pole (d) = U: UL/CSA version = R: ring tongue terminals, UL/CSA version = Blank: European version (e) = Rated Current
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
Approvals:
UL508 Listed
Voltage Rating Interrupting Capacity (UL/CSA - Ratings) Group Short Circuit (UL/CSA - Ratings) Interrupting Capacity (VDE - Ratings) Mechanical Endurance Calibration Temperature Standard Pack and Weight Terminal Size Acceptability Terminal Torque Basic Dimensions (Elevation View)
Not European standard rating. Please refer to page 21 for specific
0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 10/0.3A - 32A = 1.4kg (3.1 lb.) 40A - 63A = 1.6kg (3.5 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
applications.
DC rating (Manufacturer's self certification):
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
One pole 48VDC, two pole series 125VDC
*
16
AC Motor Starting, Across-the-line approval pending
17.5 mm (0.69 in.)
35 mm (1.38 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com
TWO POLE
THREE POLE
Basic Dimensions (side view)
35 mm (1.38 in.)
2G
Rated Current 0.3A 0.5A 0.75A 0.8A 1.0A 1.6A 2.0A 2.5A 3.0A 3.5A 4.0A 5.0A 6.0A 8.0A 10A 12A 12.5A 13A 15A 16A 20A 25A 30A 32A 40A 50A 60A 63A 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB 0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 5/1.4kg (3.1 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in. Type/ Cat. No. 2GU03 2GU05 NA 2GU08 2GU1 2GU1.6 2GU2 2GU2.5 2GU3 2GU3.5 2GU4 2GU5 2GU6 2GU8 2GU10 2GU12 2GU125 2GU13 2GU15 2GU16 2GU20 2GU25 2GU30 2GU32 2GU40 2GU50 2GU60 2GU63 Approvals
UL UL
3G
Type/ Cat. No. 3GU03 3GU05 NA 3GU08 3GU1 3GU1.6 3GU2 3GU2.5 3GU3 3GU3.5 3GU4 3GU5 3GU6 3GU8 3GU10 3GU12 3GU125 3GU13 3GU15 3GU16 3GU20 3GU25 3GU30 3GU32 3GU40 3GU50 3GU60 3GU63 480Y/277VAC 0.3-60A (RC): 10kA with UL-listed RK5 back-up fuse or MCCB
Seconds
70mm (2.76 in.)
Approvals
UL UL
V-EA-G Trip 0.3A Through 10A Rated Current
1.05-1.35xIN 60 40
Minutes
10 4 1
Thermal Overload "Must Trip" = 125% Rated Current "Must Not Trip" < 1 hr = 135% RC "Must Not Trip" > 1 hr = 105% RC "Must Not Trip" = Rated Current
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
UL UL UL UL UL UL UL UL UL
10
Tripping time t
4 1 0.4 10-1 4x10-2
Seconds
UL UL UL UL UL UL UL UL UL UL UL UL UL UL UL
10-2 4x10-3 10-3
Tripping time t
* * * * * * * * * * * *
* * * * * * * * * * * *
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
V-EA-G Trip 12A Through 63A Rated Current
1.05-1.35xIN 60 40
Minutes
10 4 1
Thermal Overload "Must Trip" = 125% Rated Current "Must Not Trip" < 1 hr = 135% RC "Must Not Trip" > 1 hr = 105% RC "Must Not Trip" = Rated Current
10 4 1 0.4 10-1 4x10-2 10-2 4x10-3 10-3
0.3-10A (RC): 10kA; 12-60A (RC): 5kA no branch circuit protection required 0.3-63A (RC): 10kA 10000 ON/OFF operations 40C (104F) 4/1.68kg (3.7 lb.) Top: 18-3 AWG; Bottom: 18-2 AWG 20 lb.in.
1
2
3 4 5 6 8 10
20
40
100
Multiple of Rated Current
"G" Magnetic Trip Parameters Rated Current, 0.3A to 63A. Magnetic Trip: 1. Hold for a minimum of 100ms at surge of 8 times rated current. 2. Trip in under 100ms at 10 times rated current. NB: Trip curves shown comply with North American standards. For trip curves according to European standards please consult Altech.
91.5 mm (3.60 in.)
91.5 mm (3.60 in.)
35 mm (1.38 in.)
52.5 mm (2.07 in.)
Altech Corp.(R) * 35 Royal Road * Flemington, NJ 08822-6000 * Phone (908)806-9400 * FAX (908)806-9490 * www.altechcorp.com 17